Description

Overview

ARI CONA®B Fig. 45.600 / 45.601 (from manufacturer datasheet 600001, Edition 05/20, AWH Armaturen-Werk Halle GmbH, a member of the ARI group) is a thermostatic bimetallic steam trap in PN40, nominal size range DN15–DN25. Fig. 600…1 is supplied with inside strainer; Fig. 601…1 (Y) with outside strainer.

The PN40 group is available in three body materials: forged steel 1.0460 (Fig. 45.600 / 45.601), high temperature steel 16Mo3 (Fig. 85.600 / 85.601) and stainless steel 1.4541 (Fig. 55.600 / 55.601). This page covers Fig. 45.600 / 45.601; shared tables are reproduced as printed in the datasheet. For ANSI versions refer to data sheet CONA®B-ANSI.

Features

  • Thermostatic steam trap with non-corrosive and robust water hammer proof bimetallic controller
  • Automatic air-venting during start up and operation of the plant
  • Check valve
  • With inside strainer (Fig. 600) or outside strainer (Fig. 601 Y)
  • Installation in any position, except screw cap downwards
  • Subcooling of condensate is continuously adjustable (observe the operation instructions)
  • Maintenance simplified due to screwed cap without sealing

Controller (chooseable for operating range):

  • Controller R13: up to inlet pressure 13 bar
  • Controller R22: up to inlet pressure 22 bar
  • Controller R32: up to inlet pressure 32 bar

Options:

  • Outside strainer with blow down valve (Pos. 46)
  • Ball valve for blow down (Pos. 56) with internal strainer (observe operating and installation instructions)

Technical data

  • Type: thermostatic bimetallic steam trap
  • Figures: Fig. 45.600 / 45.601 (Y)
  • Nominal pressure: PN40
  • Nominal size: DN15–DN25 / NPS 1/2”–1”
  • Body material: P250 GH, 1.0460 (forged steel)
  • Operating pressure PS: 32 barg at 250 °C / 22 barg at 385 °C / 14,5 barg at 450 °C
  • Allowable differential pressure ΔPMX for controllers: 32 bar (R32) / 22 bar (R22) / 13 bar (R13)
  • Types of connection: flanges …1 acc. to DIN EN 1092-1; screwed sockets …2 (Rp acc. to DIN EN 10226-1 or NPT acc. to ANSI B1.20.1); socket weld ends …3 acc. to DIN EN 12760; butt weld ends …4 (weld preparation acc. to EN ISO 9692, identification No. 1.3 and 1.5)

Parts

Datasheet page 5, table reproduced in full (PN40 group):

Pos.Sp.p.DescriptionFig. 45.600 / 45.601Fig. 85.600 / 85.601Fig. 55.600 / 55.601
1BodyP250 GH, 1.046016Mo3, 1.5415X6CrNiTi18-10, 1.4541
2xStrainerX5CrNi18-10, 1.4301samesame
6CapP250 GH, 1.046016Mo3, 1.5415X6CrNiTi18-10, 1.4541
7xStrainerX5CrNi18-10, 1.4301samesame
8xStrainer plugX6CrNiTi18-10, 1.4541samesame
24xController, cpl.TB 102 / 85 (corrosion resistant bimetal)samesame
46xBlow down valve, cpl.X6CrNiTi18-10, 1.4541samesame
56xBall valve for blow down (G 3/8”)GX5CrNiMo19-11-2, 1.4408samesame

Dimensions and weights

Datasheet page 5, table reproduced in full (PN40, DN15–DN25):

ItemDN15 flangesDN20 flangesDN25 flangesDN15 screwed socketsDN20 screwed socketsDN25 screwed socketsDN15 socket weldDN20 socket weldDN25 socket weldDN15 butt weldDN20 butt weldDN25 butt weld
NPS1/2”3/4”1”1/2”3/4”1”1/2”3/4”1”1/2”3/4”1”
L (mm)150150160959595250250250250250250
H (mm)9898989898103989898989898
H1 (mm)626262626255626262626262
S (mm)707070707070707070707070
S1 (mm)303030303030303030303030
HEX (mm)505050505050505050505050
Weight Fig. 600/601 (approx.) (kg)3,23,74,21,71,62,12,22,32,42,22,32,4

Capacity chart

The capacity chart shows the maximum capacity at factory setting. (Other factory-settings for the sub-cooling on request.)

  • Curve 1: Maximum flow of hot condensate at approx. 10 K below saturation temperature.
  • Curve 2: Maximum flow of sub-cooled condensate at approx. 30 K below saturation temperature (with back-up of condensate).
  • Curve 3: Maximum flow at cold condensate at about 20 °C (during start-up of a cold installation).

The condensate temperature determines the opening of the controller. Capacity is increased with the sub-cooling temperature of the condensate.

Ordering information

Please indicate when ordering: Figure-No. (45.600 or 45.601), nominal pressure (PN40), nominal diameter, controller range (R13/R22/R32), type of connection.

For a quotation on the ARI CONA®B Fig. 45.600 / 45.601, please send the figure no., DN, PN and quantity.