Description
Overview
ARI CONA®B Fig. 86.600 and Fig. 87.600 (from manufacturer datasheet 600001, Edition 05/20) are high pressure bimetallic steam traps in high temperature steel. The body and cover are 16Mo3, 1.5415. Fig. 86.600 covers PN63 (DN15–DN50), Fig. 87.600 covers PN100 (DN15–25). Operating pressure depends on inlet temperature: for Fig. 86.600 PN63 DN15-25, 46 barg at 425 °C and 45 barg at 450 °C with controller R46; for Fig. 87.600 PN100, 90 barg at 450 °C, 56 barg at 500 °C and 27 barg at 530 °C with controllers R56/R90. For DN40-50, Fig. 86.600 PN63 allows 56 barg at 300 °C, 50 barg at 350 °C and 45 barg at 450 °C with controllers R56/R32.
For ANSI versions refer to data sheet CONA®B-ANSI.
Features
- Thermostatic steam trap with non-corrosive and robust water hammer proof bimetallic controller
- Steam trap specially for high pressures
- Automatic air-venting during start up and operation of the plant
- Check valve
- With inside strainer
- Installation in any position, except screw cap downwards
- Subcooling of condensate is continuously adjustable (observe the operation instructions)
- Maintenance simplified due to screwed cap without sealing
- The controller may be changed without disturbing the pipe work
Technical data
- Type: high pressure bimetallic steam trap (thermostatic)
- Figures: Fig. 86.600 (PN63), Fig. 87.600 (PN100)
- Nominal size: DN15–25 (NPS 1/2”–1”) for Fig. 86.600/87.600; DN40–50 (NPS 1 1/2”–2”) for Fig. 86.600
- Material: 16Mo3, 1.5415 (body, cover)
- Controllers (chooseable for operating range): R32 up to inlet pressure 32 bar, R46 up to 46 bar, R56 up to 56 bar, R90 up to 90 bar
- Connection types: flanges …1 acc. to DIN EN 1092-1, socket weld ends …3 acc. to DIN EN 12760, butt weld ends …4 with weld preparation acc. to EN ISO 9692 identification No. 1.3 and 1.5
- Face-to-face: acc. to data sheet resp. customer request
Parts and materials
Datasheet parts table for Fig. 86.600 / 87.600 (PN63/PN100) reproduced in full (x = spare part):
| Pos. | Sp.p. | Description | Fig. 86.600 / 87.600 |
|---|---|---|---|
| 1 | Body | 16Mo3, 1.5415 | |
| 2 | x | Strainer | X5CrNi18-10, 1.4301 |
| 6 | Cover | 16Mo3, 1.5415 | |
| 24 | x | Controller, cpl. | TB 102 / 85 (corrosion resistant bimetal) |
| 26 | x | Gasket | Graphite (CrNi laminated with graphite) |
| 28 | Hexagonal nut | 21CrMoV 5-7, 1.7709 | |
| 29 | x | Erosion deflector | X8CrNiS18-9, 1.4305 |
| 30 | Extension sleeve | 21CrMoV 5-7, 1.7709 | |
| 36 | Stud | 21CrMoV 5-7, 1.7709 |
Dimensions and weights
Datasheet page 10 (PN63/PN100, DN15-25), tables reproduced in full:
| Item | Flanges DN15 | DN20 | DN25 | Socket weld DN15 | DN20 | DN25 | Butt weld DN15 | DN20 | DN25 |
|---|---|---|---|---|---|---|---|---|---|
| L (mm) | 210 | 210 | 230 | 95 | 95 | 95 | 250 | 250 | 250 |
| H (mm) | 98 | 98 | 98 | 98 | 98 | 103 | 98 | 98 | 98 |
| S (mm) | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 |
| HEX (mm) | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
| Weight Fig. 600 approx. (kg) | 4,1 | 5,6 | 7 | 1,7 | 1,6 | 2,1 | 2,2 | 2,3 | 2,4 |
Datasheet page 13 (PN63, DN40-50), tables reproduced in full (please indicate dimension of the tube when ordering for butt weld ends):
| Item | Flanges DN40 | DN50 | Socket weld DN40 | DN50 | Butt weld DN40 | DN50 |
|---|---|---|---|---|---|---|
| L (mm) | 260 | 300 | 130 | 210 | 250 | 250 |
| H (mm) | 144 | 144 | 144 | 144 | 144 | 144 |
| S (mm) | 90 | 90 | 90 | 90 | 90 | 90 |
| SQR (mm) | 110 | 110 | 110 | 110 | 110 | 110 |
| Weight Fig. 600 approx. (kg) | 13,3 | 14,1 | 8 | 8 | 8,9 | 9,8 |
Standard-flange dimensions acc. to DIN EN 1092-1/-2 (datasheet page 23, PN63 and PN100 rows):
| Item | DN15 | DN20 | DN25 | DN32 | DN40 | DN50 |
|---|---|---|---|---|---|---|
| PN63 ØD (mm) | 105 | 130 | 140 | — | 170 | 180 |
| PN63 ØK (mm) | 75 | 90 | 100 | — | 125 | 135 |
| PN63 n x Ød (mm) | 4 x 14 | 4 x 18 | 4 x 18 | — | 4 x 22 | 4 x 22 |
| PN100 ØD (mm) | 105 | 130 | 140 | — | — | — |
| PN100 ØK (mm) | 75 | 90 | 100 | — | — | — |
| PN100 n x Ød (mm) | 4 x 14 | 4 x 16 | 4 x 18 | — | — | — |
Capacity chart
The capacity chart shows the maximum flow at factory setting. For operating pressures below 5 bar, a correction of the factory-setting acc. to manufacturer’s information is recommended. Curve 1: maximum flow of hot condensate approx. 15 K below saturation temperature. Curve 2: maximum flow of sub-cooled condensate at approx. 30 K below saturation temperature (with back-up of condensate). Curve 3: maximum flow at cold condensate at about 20 °C (during start-up of a cold installation).
Ordering information
Selection criteria: steam pressure, back pressure, quantity of condensate, nominal diameter / pressure, pipe-connection, controller, material, place of service or kind of steam consumer. Datasheet order example: Bimetallic steam trap CONA®B, Fig. 600, PN40, DN15, 1.0460, Controller R22, with flanges, face-to-face dimension 150 mm.
Specify Fig. 86.600 or 87.600, DN, PN, controller and quantity when requesting a quotation.