Description

Overview

ARI CONA® TD Fig. 56.641 (Y) is a thermodynamic steam trap of stainless steel for the condensate discharge from all kinds of steam systems. The trap covers nominal diameters DN10 to DN25 (NPS 3/8” to 1”) at PN63 with an operating temperature range from -10°C up to 400°C at 42 bar.

Features

  • Intermittent mode of operation
  • Robust and resistant to water-hammer
  • It acts as a check valve in the event of reverse flow
  • With outside strainer
  • Can be installed in any position, except with the cap facing downwards
  • Optimized design for quick installation
  • Maintenance simplified due to screwed cap without sealing

ARI CONA TD Fig. 56.641 cutaway section

Technical Data

ParameterSpecification
FigureFig. 56.641 (Y)
Nominal pressurePN63
Body materialASTM A743 CA40
Nominal diameter / NPS10 - 25 / 3/8” - 1”
Max. allowable pressure PMA63 bar @120°C
Min. allowable temperature TSmin-10°C
Max. allowable temperature TMA400°C @42 bar
Allowable differential pressure ΔPMX42 bar
Perm. pressure ratioBack pressure / Inlet pressure ≤ 0,8 barg
Min. operating pressure1 barg

For versions rated to Class 400 refer to data sheet CONA® TD-ANSI.

Types of Connection

ConnectionCodeStandard
Screwed sockets…2Rp thread acc. to DIN EN 10226-1 or NPT thread acc. to ANSI B1.20.1
Socket weld ends…3acc. to DIN EN 12760

Other types of connection on request.

Parts

Pos.Sp.p.DescriptionFig. 56.641
1BodyA743CA40
6CapSA479Gr.304
7xStrainerSA240Gr.304
8Strainer plugSA479Gr.304
25xDiscAISI420

Sp.p. = Spare parts.

Dimensions and Weights

Face-to-face acc. to data sheet resp. customer request.

Types of connectionScrewed sockets (NPS 3/8” - 1”) / Socket weld ends (DN 10-25) ×4
DN10 · 15 · 20 · 25
NPS3/8” · 1/2” · 3/4” · 1”
L (mm)78 · 78 · 90 · 95
H (mm)47 · 47 · 47 · 60
H1 (mm)51 · 53 · 53 · 58
S (mm)20 · 20 · 20 · 20
S1 (mm)45 · 45 · 45 · 45
HEX (mm)36 · 36 · 36 · 43
Connection dimensions standard socket weld end: ød (mm)17.8 · 22 · 27.3 · 34
Connection dimensions standard socket weld end: t (mm)10 · 10 · 13 · 13
Weight Fig. 641, approx. (kg)0,8 · 0,9 · 0,9 · 1,5

ARI CONA TD Fig. 56.641 dimensional drawing

Capacity

The capacity chart shows the maximum flow of hot condensate for the standard controller. Flow rate of cold condensate at 20°C is about 1,5 times the volume of hot condensate.

ARI CONA TD Fig. 56.641 capacity chart

Ordering Information

Selection criteria: steam pressure, back pressure, quantity of condensate, nominal diameter / pressure, type of connection, material, place of service or kind of steam consumer.

Example for order data: Thermodynamic steam trap CONA® TD, Fig. 56.641, PN63, DN20, A743CA40, with screwed sockets.

Specify CONA® TD Fig. 56.641, DN, connection type, and quantity when requesting a quotation.